继电保护原理与应用(第三版)3.1-3.5(22)

2023-05-02 来源:飞速影视
在变压器极性的定义中,电压降规则通常被忽略,但它是通过Y形-三角形变压器组检查相位关系的一个非常有用的工具,或者在连接变压器组以获得电力系统所需的特定相移时,它是一个非常有用的工具。ANSI=IEEE变压器标准规定,采用Y形三角形或三角形Y形组时,高压应领先低压308。因此,如果高压侧为Y形,则需要不同的连接,如果高压侧为三角形,则需要不同的连接。这两种情况的连接如图3.6所示。三相变压器连接的下图说明了使用压降规则来提供或检查连接。这些电压降上的箭头已被省略(最好不使用),因为它们不是必需的,并且可能导致混淆。
In Figure 3.6a, the check is made by noting that a to n from polarity to nonpolarity on the left-side winding is in phase with A to B from polarity to nonpolarity on the right-side winding. Similarly, b to n (polarity to nonpolarity) is in phase with B to C (polarity to nonpolarity) across the middle transformer, and c to n (polarity to nonpolarity) is in phase with C to A (polarity to nonpolarity) across the lower transformer. From this, by comparing the line-to-neutral voltages on the two sides, it is observed that phase-a-to-n voltage leads phase-A-to-neutral voltage. Accordingly, the wye side would be the high-voltage side if this is an ANSI=IEEE standard transformer.
在图3.6a中,通过注意左侧绕组从极性到非极性的a到n与右侧绕组从极性到非极性的a到B同相进行检查。类似地,b到n(极性到非极性)与中间变压器上的b到C(极性到非极性)同相,C到n(极性到非极性)与下部变压器上的C到A(极性到非极性)同相。由此,通过比较两侧的线对中性点电压,可以看出a-n相电压领先于a-n相电压。因此,如果这是ANSI=IEEE标准变压器,则Y形端将是高压侧。
相关影视
合作伙伴
本站仅为学习交流之用,所有视频和图片均来自互联网收集而来,版权归原创者所有,本网站只提供web页面服务,并不提供资源存储,也不参与录制、上传
若本站收录的节目无意侵犯了贵司版权,请发邮件(我们会在3个工作日内删除侵权内容,谢谢。)

www.fs94.org-飞速影视 粤ICP备74369512号